Governor Model: WSIEG1
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < T3 < 0.25*Mult*TimeStep then T3 = 0.0
ElseIf 0.25*Mult*TimeStep < T3 < 0.5*Mult*TimeStep then T3 = 0.5*Mult*TimeStep - If Uo < Uc then swap the values. If Uo < 0 then Uo change sign to positive. If Uc > 0 then change sign to negative.
- If Pmax < Pmin then swap the values.
- K1 to K8: Check K1+K3+K5+K7 and K2+K4+K6+K8 <= 1.0 and if not normalized values to 1.0.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Gate > Pmax , then Pmax = Gate or if Gate < Pmin , then Pmin = Gate
Model Equations and/or Block Diagrams
Parameters:
| K | Governor gain (recirpocal of droop), pu |
| T1 | Governor mechanism time constant, sec |
| T2 | Turbine power time constant, sec |
| T3 | Turbine exhaust temperature time constant, sec |
| Uo | Maximum valve opening velocity, pu/sec |
| Uc | Maximum valve closing velocity, pu/sec |
| Pmax | Maximum gate opening, pu of mwcap |
| Pmin | Minimum gate opening, pu of mwcap |
| T4 | Governor lead time constant, sec |
| K1 | Fraction of hp shaft power after first boiler pass |
| K2 | Fraction of lp shaft power after first boiler pass |
| T5 | Governor lag time constant, sec |
| K3 | Fraction of hp shaft power after second boiler pass |
| K4 | Fraction of lp shaft power after second boiler pass |
| T6 | T, sec |
| K5 | Fraction of hp shaft power after third boiler pass |
| K6 | Fraction of lp shaft power after third boiler pass |
| T7 | T, sec |
| K7 | Fraction of hp shaft power after fourth boiler pass |
| K8 | Fraction of lp shaft power after fourth boiler pass |
| db1pu | Intentional deadband width, pu |
| Err | Intentional db hysteresis, pu |
| db2pu | Unintentional deadband, pu |
| Gv1 | Nonlinear gain point 1, pu gv |
| Pgv1 | Nonlinear gain point 1, pu power |
| Gv2 | Nonlinear gain point 2, pu gv |
| Pgv2 | Nonlinear gain point 2, pu power |
| Gv3 | Nonlinear gain point 3, pu gv |
| Pgv3 | Nonlinear gain point 3, pu power |
| Gv4 | Nonlinear gain point 4, pu gv |
| Pgv4 | Nonlinear gain point 4, pu power |
| Gv5 | Nonlinear gain point 5, pu gv |
| Pgv5 | Nonlinear gain point 5, pu power |
| Iblock | Pmin and Pmax initialization. |